System boundary and model
For a steady, single-phase liquid stream, use P = m_dot × cp × (Tin − Tout). Mass-flow rate m_dot is in kg/s; the chosen constant cp is 4.18 kJ/(kg·K). Temperature differences have the same numerical value in K and °C. The result is thermal power in kW.
Worked example and sensitivity
At 5 kg/s, Tin = 120 °C and Tout = 50 °C: P = 5 × 4.18 × 70 = 1463 kW. Increasing flow to 5.5 kg/s at the same temperatures gives 1609.3 kW, a 10% increase. This proportional response follows from fixed cp and temperature drop.
Assumptions that matter
Assume sufficient pressure to keep the water liquid throughout. Hold cp and outlet temperature fixed; neglect heat loss, kinetic and potential energy changes. The model does not resolve exchanger capacity, pressure loss, pumping power, phase change or reservoir cooling.
What would validate this model?
Measure inlet/outlet temperature, mass flow, pressure and heat losses; select properties for the actual fluid and conditions. Compare calculated heat with an independent heat balance. Thermal kW is not electrical kW, annual energy or a guarantee of usable plant output.